Viewing Product

The VX-2000 System Manager has been designed and built to meet British and European standards: BS5839 part 8 and EN 60849. The VX-2000 is an input matrix unit that assigns input signals to 4 audio buses, and functions as the VX-2000 system's main controller.
A total of up to 8 units of the VX-200XI, VX-200XR, and 900 Series input modules can be mounted in a System Manager.
The VX-2000 can control audio signal routing, priorities, and peripheral equipment, while input and output control settings are performed by way of a PC.
Up to 2,000 system events and failures can also be recorded, and the log can be viewed from a PC.
| Specification | |
|---|---|
| Power Source | 24V DC (operating range: 20 - 40V DC) M3.5 screw terminal, distance between barriers: 8.8m |
| Current consumption | Under 650mA (20V DC) |
| Input | -20dB*, unbalanced, Number of module slots: 8 Usable module: VX-200XR, VX-200XI, 900 series plug-in modules (M-01F, M-01M,M-01P, M-01S, M-03P, M-51F, M-51S, M-61F, M-61S, U-01F, U-01P, U-01R,U-01S, U-61S) |
| Audio Link Output | Number of audio buses: 4 0dB*, electronically balanced, RJ45 female connector Twisted-pair straight cable (TIA/EIA-568A standard) |
| Monitor Output | 0dB*, electronically balanced, XLR receptacle (3 pins). |
| Frequency response | 20 - 20,000Hz |
| Signal to Noise Ratio | Over 60dB |
| Distortion | Under 0.5% |
| Cross Talk | Under -60dB (1kHz, 0dB*) |
| Control Input | 16 inputs, no-voltage make contact, open voltage: 17V DC, Short circuit current: Under 5mA, RJ45 connector x 2 C |
| Control Output | 16 outputs, open collector output, withstand voltage: 30V DC, Control current: Under 5mA, RJ45 connector x 2 C |
| Chime tone | Built-in chime: 4-tone chime (up)/4-tone chime (down)/2-tone chime/Gong |
| Communication system | PC (Setting software to be installed): D-sub connector (9 pins), cross cable, RS-232C VX-2000SF: RJ45 female connector, Twisted-pair straight cable (TIA/EIA-568A standard), LONWORDS RS-485 |
| Operating temperature | 0ēC to +40ēC |
| Finish | Panel: Surface-treated steel plate, black, 30% gloss, paint |
| Dimensions | 482 (W) x 132.6 (H) x 337 (D)mm |
| Weight | 6.4kg |
| Accessory | Rack mounting bracket (preinstalled on the unit) x 2, Rack mounting screw x 4, Fiber washer x 4, Blank panel x 7, Blank panel mounting screw x 14, Setting software installation CD x 1, Fuse (T1.6A L) x 1/(T6.3A L) x 1 |
| Option | Voice announcement board: EV-200, Isolation transformer: IT-450 (audio link output) |
| * 0 dB = 1 V | |
| Note: | LONWORKS is a trademark of Echelon Corporation. |
For balanced, low impedance mics. Including Gain Control.
Input module for 900 Series Amplifiers/VX-2000 System Manager for unbalanced, line level equipment such as AM/FM tuners, tape decks, MP3 players or CD players.
Including gain control.
- Input module for 900 Series Amplifiers/VX-2000 System Manager for unbalanced, line level equipment such as AM/FM tuners, tape decks, MP3 players or CD players.
- Including gain control.
For unbalanced, line level equipment such as AM/FM tuners, tape decks and CD players. Including Gain Control and high/low cut filters.
VX-200XI
The VX-200XI module is designed to be used in conjunction with the VX-2000 System Manager, and comes with control input terminals, low-cut and high-cut filters, and gain controls.
VX-200XR
The VX-200XR module is designed to be used with the RM-200X Remote microphone or RM-200XF Fireman's Microphone. Insert this module into the VX-2000's input module slot for each Remote or Fire Microphone(s) used in the system.
VX-2000DS
Emergency Power Supply Unit The VX-2000DS Emergency Power Supply Unit supplies the DC power to each equipment in the VX-2000 system by connecting the VX-200PS Power Supply Unit. It keeps the battery unit that contains 2 × 12 V sealed lead batteries charged compensating for the temperature of the battery charging voltage. When the DC power supply from the VX-200PS stops, the VX-2000DS is automatically switched to the backup battery. The VX-2000DS is certified with EN 54-4.
VX-2000SF
The VX-2000SF Surveillance Frame is the output matrix section of the VX-2000 system that assigns audio signals to individual zones from 4 audio buses. It can be extended to up to 5 units.
A total of 10 units of output modules and control modules can be installed per VX-2000SF.
Followung modules can be used:
VX-200SP Pilot Tone Detection module
VX-200SP-2 Pilot Tone Detection module with end-of-line module
VX-200SZ-2 Impedance Detection module with A/B loudspeaker lines
VX-200SI Control Input module
VX-200SO Control Output module
VX-200PS
The VX-200PS Power Supply Unit is mounted in the VX-2000PF Power Supply Frame when in use. There are 2 DC output channels per unit. Use the VX-200PS in the number suited to the required total system power.






Download now VX-2000_Cookbook_E.pdf
Download now VX-2000 Firmware.zip