The VX-2000 System Manager has been designed and built to meet British and European standards: BS5839 part 8 and EN 60849. The VX-2000 is an input matrix unit that assigns input signals to 4 audio buses, and functions as the VX-2000 system's main controller.

A total of up to 8 units of the VX-200XI, VX-200XR, and 900 Series input modules can be mounted in a System Manager.
The VX-2000 can control audio signal routing, priorities, and peripheral equipment, while input and output control settings are performed by way of a PC.

Up to 2,000 system events and failures can also be recorded, and the log can be viewed from a PC.

Specification
Power Source 24V DC (operating range: 20 - 40V DC)
M3.5 screw terminal, distance between barriers: 8.8m
Current consumption Under 650mA (20V DC)
Input -20dB*, unbalanced, Number of module slots: 8
Usable module: VX-200XR, VX-200XI, 900 series plug-in modules (M-01F, M-01M,M-01P, M-01S, M-03P, M-51F, M-51S, M-61F, M-61S, U-01F, U-01P, U-01R,U-01S, U-61S)
Audio Link Output Number of audio buses: 4 0dB*, electronically balanced, RJ45 female connector
Twisted-pair straight cable (TIA/EIA-568A standard)
Monitor Output 0dB*, electronically balanced, XLR receptacle (3 pins).
Frequency response 20 - 20,000Hz
Signal to Noise Ratio Over 60dB
Distortion Under 0.5%
Cross Talk Under -60dB (1kHz, 0dB*)
Control Input 16 inputs, no-voltage make contact, open voltage: 17V DC, Short circuit current: Under 5mA, RJ45 connector x 2 C
Control Output 16 outputs, open collector output, withstand voltage: 30V DC, Control current: Under 5mA, RJ45 connector x 2 C
Chime tone Built-in chime: 4-tone chime (up)/4-tone chime (down)/2-tone chime/Gong
Communication system PC (Setting software to be installed): D-sub connector (9 pins), cross cable, RS-232C
VX-2000SF: RJ45 female connector, Twisted-pair straight cable (TIA/EIA-568A standard), LONWORDS RS-485
Operating temperature 0ēC to +40ēC
Finish Panel: Surface-treated steel plate, black, 30% gloss, paint
Dimensions 482 (W) x 132.6 (H) x 337 (D)mm
Weight 6.4kg
Accessory Rack mounting bracket (preinstalled on the unit) x 2, Rack mounting screw x 4, Fiber washer x 4, Blank panel x 7, Blank panel mounting screw x 14, Setting software installation CD x 1, Fuse (T1.6A L) x 1/(T6.3A L) x 1
Option Voice announcement board: EV-200, Isolation transformer: IT-450 (audio link output)
* 0 dB = 1 V
Note: LONWORKS is a trademark of Echelon Corporation.
Microphone Input Module with XLR connector

For balanced, low impedance mics. Including Gain Control.

Unbalanced Auxiliary Input Module with XLR connector

Input module for 900 Series Amplifiers/VX-2000 System Manager for unbalanced, line level equipment such as AM/FM tuners, tape decks, MP3 players or CD players.
Including gain control.

Auxiliary Input Module with 3 pin Screw Terminal

  • Input module for 900 Series Amplifiers/VX-2000 System Manager for unbalanced, line level equipment such as AM/FM tuners, tape decks, MP3 players or CD players.
  • Including gain control.
Unbalanced Line Input with RCA connectors

For unbalanced, line level equipment such as AM/FM tuners, tape decks and CD players. Including Gain Control and high/low cut filters.

Audio Input Module

The VX-200XI module is designed to be used in conjunction with the VX-2000 System Manager, and comes with control input terminals, low-cut and high-cut filters, and gain controls.

Remote Microphone Input Module

The VX-200XR module is designed to be used with the RM-200X Remote microphone or RM-200XF Fireman's Microphone. Insert this module into the VX-2000's input module slot for each Remote or Fire Microphone(s) used in the system.

EN 54-4 Emergency Power Supply Unit

Emergency Power Supply Unit The VX-2000DS Emergency Power Supply Unit supplies the DC power to each equipment in the VX-2000 system by connecting the VX-200PS Power Supply Unit. It keeps the battery unit that contains 2 × 12 V sealed lead batteries charged compensating for the temperature of the battery charging voltage. When the DC power supply from the VX-200PS stops, the VX-2000DS is automatically switched to the backup battery. The VX-2000DS is certified with EN 54-4.

VX-2000SF

Surveillance Frame

The VX-2000SF Surveillance Frame is the output matrix section of the VX-2000 system that assigns audio signals to individual zones from 4 audio buses. It can be extended to up to 5 units.
A total of 10 units of output modules and control modules can be installed per VX-2000SF.

Followung modules can be used:
VX-200SP Pilot Tone Detection module
VX-200SP-2 Pilot Tone Detection module with end-of-line module
VX-200SZ-2 Impedance Detection module with A/B loudspeaker lines
VX-200SI Control Input module
VX-200SO Control Output module

EN 54-4 Power Supply Unit

The VX-200PS Power Supply Unit is mounted in the VX-2000PF Power Supply Frame when in use. There are 2 DC output channels per unit. Use the VX-200PS in the number suited to the required total system power.